Product Description: WP series thermocouple isolation temperature transmitter, it comes from the scene of the thermoelectrical potential of thermocouple is converted to a linear relationship with temperature (4~ 20) mA (1~ 5) DC or V Dc isolation signal output has a cold end automatic compensation function.
Product features
Explosion proof mark: [Exia]Ⅱ C
Power supply:24V;2V
Power consumption: about 1.5W (24V power supply,20mA output )
Danger zone: input signal J, K, T, E, S, B, R thermocouple
Safety zone output: WP6000-EX WP6000-EX ( V )
Signal: (4~ 20) mA (1~ 5) V
Load resistance:≤ 500 Ω250KΩ=
The accuracy of the output:0.5
The compensation accuracy:1/20 ℃( compensation resistance: Cu50copper resistance)
Temperature drift:0.01% F.S/℃
Working temperature:0℃ to +50 ℃
The national explosion-proof electrical product quality supervision and Inspection Center ( CQST ) authentication parameters (9,10terminals ).
Uo:4V, Io:90mA, Co:100 μF, Lo:4.2mH, Po:0.09W, Um:250V AC/DC
Applicable to the field device:J, K, T, E, S, B, R thermocouple sensor.