Product brief introduction: DBW electric two-wire temperature transmitter belongs to DDZ- type electric unit combination instrument transmission unit, with the regulator, the actuator indicator, recorder can be composed of automatic adjusting circuit, or indicating circuit.
The transmitter for the on-site installation type.
Two wire transmitter by the output signal (4mA DC ) affect the lower limit generally no linear correction circuit, so the output of the transmitter only with the MV ( TC),△ R ( RTD ) proportional to. In order to realize the accurate temperature engineering quantity indication, the series and configuration of the two instrumentation ( controller, indicator, recorder ) scale is associated with the temperature measurement element mv ( or R) - temperature characteristics consistent.
Output signal:4~ 20mA
Precision: the input signal is greater than or equal to 5mV (△ R ≥10 Ω)0.5
3 mV (≤6Ω) input signal (△ R ) < 5( mV10Ω)1
1.5 mV (≤3Ω) input signal (△ R ) < 3( mV6Ω)1.5
The package containing the resistance:250 Ωto 450 Ω
Power supply and method:24V DC generally by double isolation type distribution of electrical power supply
Environmental conditions:
Temperature of -25℃ ~60C
Temperature≤ 95%RH
Vibration f≤ 60Hz
Double amplitude < 0.02mm
Ambient air does not contain corrosive gases, chrome, nickel plating, nonferrous metals and their alloys corrode medium
Power: 0.5W
Explosion proof type and grade of flame-proof type: dIIBT4
Intrinsically safe explosion-proof type iaIICT6
D electric unit combination instrument
B transmission unit
W temperature
3) the second transmission temperature transmitter
4) the second transmission MV transmission
- 1) thermocouple
2) the thermal resistance
3) the thermocouple temperature difference
4) the thermal resistance temperature
- 1) E or Cu50
2) K or Cu100
3) S or Pt50
4) B or BA2Pt100
- O/B improvement program
- ia intrinsically safe explosion proof
D flameproof type not expressed as general type